The DPV1 command channel
DPV1 command 9dec (09hex):
change the extended ID code 1 in the connected AS-i slave
11-16
11.10
DPV1 command 9
dec
(09
hex
):
change the extended ID code 1 in the connected AS-i slave
Request of DPV1 master
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
user ID
command request = 65
hex
2
00
command number = 09
hex
= 9
dec
3
ignored A/B
slave
address
4
ignored
new "Extended ID code 1"
5…17
ignored
18…19
reserved
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0F65
0F = user ID changes e.g. to 15
65 = command request
2
0009
09 = command number 9
3
0011
11 = slave address 17(A)
4
0008
new "Extended ID code 1" = 8
Response from controllere (DPV1 slave) in the normal case
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
reflected user ID
command status = 6F
hex
2
00
reflected command number = 09
hex
Example:
Word no.
Value [hex]
Description
1 0F6F
0F = reflected user ID changes e.g. to 15
6F = command status is "ready" (no fault)
2
0009
09 = reflected command number 9
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...