DP module 12: Extended command channel
Module 12, extended command 3:
adopt and store connected AS-i slaves in the configuration
9-10
Response from controllere (gateway) in case of an error
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=1 B=0
M
0/1
reflected user ID
reflected command number = 03
hex
2
reserved = 0
3
0 error
code
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 1C03
E=1: fault occurred during execution of the command
M=0: AS-i master 1
xC = reflected user ID 12
03 = reflected command number 3
2 0000
reserved
3
0014
error code 14
hex
= master is in wrong operating mode
Possible error codes
Value [hex]
Description
14
master is in the wrong operating mode
here: master is not in the normal mode