DP module 12: Extended command channel
Module 12, extended command 6:
readdress a connected AS-i slave
9-15
9.10
Module 12, extended command 6:
readdress a connected AS-i slave
Request of DP master
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
R R
M
0/1
user ID
Command number = 06
hex
= 06
dec
2
reserved = 0
reserved = 0
3
0 0
0
A/B
0/1
old slave address
4
0 0
0
A/B
0/1
new slave address
5…18
not used
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0806
M=0: AS-i master 1
08 = user ID changes e.g. to 8
06 = command number 6
2 0000
reserved
3 0029
old slave address 9B
(for B slaves: bit 5 = 1
→
add 20
hex
to the address)
4
000B
new slave address 11A
Response from controllere (gateway) in the normal case
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=0 B=0
M
0/1
reflected user ID
reflected command number = 06
hex
2…18
not changed
Legend
→
page
Example:
Word no.
Value [hex]
Description
1
0
806
M=0: AS-i master 1
08 = reflected user ID 8
06 = reflected command number 6
2…18 0000
not
changed
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...