The DPV1 command channel
DPV1 command 97dec (61hex):
carry out various settings in the controllere
11-66
11.33
DPV1 command 97
dec
(61
hex
):
carry out various settings in the controllere
Request of DPV1 master
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
user ID
command request = 65
hex
2
00
command number = 61
hex
= 97
dec
3
00 command
number
4…19
parameters 1…16
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0865
08 = user ID changes e.g. to 8
65 = command request
2
0061
61 = command number 97
3 0010
Command number:
10 = changes the operating mode of the PLC (corresponding parameters
→
word 4)
Further command numbers:
12 = reset all slave error counters
13 = reset the configuration error counter
14 = reset AS-i cycle error counter
4 0002
Parameters; here for command number 10:
0000 = activates the gateway mode
0001 = stops the PLC
0002 = sets the operation mode of the PLC to RUN
Response from controllere (DPV1 slave)
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
reflected user ID
command status = 6F
hex
2
00
reflected command number = 61
hex
3...18
00 00
Example:
Word no.
Value [hex]
Description
1 086F
08 = reflected user ID 8
6F = command status is "ready" (no fault)
2
0061
61 = reflected command number 97
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...