DP module 7: Command channel
Module 7, command 9:
read LDS (list of detected slaves)
8-11
8.10
Module 7, command 9:
read LDS (list of detected slaves)
The 2 feedback bytes can only give information about max. 16 slaves. Therefore the slaves are
divided into 4 groups (
→
table page
Structure
Request of DP master
Bit
MM = master no. (1…2)
Byte
7
6
5
4
3
2
1
0
1
0 0
09
hex
X = slave type (0…1)
0 = standard / A slave
1 = B slave
2
MM X
SSSSS
SSSSS = slave no. (0…31
dec
)
3
0
not used *)
4
0
not used *)
Response from controllere
Bit
Byte
7
6
5
4
3
2
1
0
1
D7 D6
0
2
0
D6 = command code
D7 = error code
→
page
, table at the bottom
3
→
4
→
provides the addresses of the detected slaves in this
address group
Example: Read LDS (list of detected slaves) of slave group 3 on AS-i master 2
Request of DP master
Byte no.
Value [hex]
Description
1
09
09 = command 9
2 A5
(slave no.
5
)
→
group 3
+ (master no.
2 * 64
)
+ (
32
, if B slave)
= 165
dec
=
A5
hex
3
00
not used *)
4
00
not used *)
Response from controllere
Byte no.
Value [hex]
Description
1 00
2 00
3
03
hex
=
00000011
bin
→
table page
group 3:
slaves 8B and 9B were detected
4
FE
hex
=
11111110
bin
→
table page
group 3:
slaves 1B to 7B were detected
*)
IMPORTANT:
For the query read only the required bytes. Unused bytes can contain information of
previous queries.
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...