DP module 12: Extended command channel
Module 12, extended command 3:
adopt and store connected AS-i slaves in the configuration
9-9
9.7
Module 12, extended command 3:
adopt and store connected AS-i slaves in the configuration
Request of DP master
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
R R
M
0/1
user ID
command number = 03
hex
= 03
dec
2…18
not used
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0C03
M=0: AS-i master 1
0C = user ID changes e.g. to 12
03 = command number 3
2…18 0000
not
used
Response from controllere (gateway) in the normal case
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=0 B=0
M
0/1
reflected user ID
reflected command number = 03
hex
2…18
not changed
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0C03
M=0: AS-i master 1
0C = reflected user ID 12
03 = reflected command number 3
2 0000
not
changed