DP module 12: Extended command channel
Module 12, extended command 5:
set the operating mode of the AS-i master
9-14
Response from controllere (gateway) in case of an error
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=1 B=0
M
0/1
reflected user ID
reflected command number = 05
hex
2
reserved = 0
reserved = 0
3
0 error
code
4…18
ignored
Legend
→
page
Example:
Word no.
Value [hex]
Description
1
8
105
E=1: fault occurred during execution of the command
M=0: AS-i master 1
01 = reflected user ID 1
05 = reflected command number 5
2 0000
reserved
3
0003
error code 03
hex
= slave with the address 0 connected
Possible error codes
Value [hex]
Description
03
slave with the address 0 is connected