DP module 12: Extended command channel
Module 12, extended command 31dec (1Fhex):
one-time execution of the "Extended safety monitor protocol" in the "Safety at work" monitor
9-34
Response from controllere (gateway) in case of an error
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=1 B=0 M=0
reflected user ID
reflected command number = 1F
hex
2
reserved = 0
reserved = 0
3
0 error
code
4…18
ignored
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 871F
E=1: error during command execution
07 = reflected user ID 7
1F = reflected command number 31
2 0000
reserved
3 0011
error code 11
hex
→
no slave with the profile S-7.F.F
Possible error codes
Value [hex] Description
00…02
general errors during command processing
0A…0C
internal protocol error
10
sub command invalid
11
no slave with the profile S-7.F.F on the slave address
16
the protocol mode of the monitor at the address was changed
20
it was not possible to process the command within the specified time
EE
fatal error during command execution
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...