DP module 12: Extended command channel
Module 12, extended command 35dec (23hex):
write parameter character string of an AS-i slave with the profile S-7.4
9-39
Response from controllere (gateway)
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=0
S
0/1
M
0/1
reflected user ID
reflected command number = 23
hex
2
R
R
slave address
F=0
R
R
number of bytes to be sent
3…18
not changed
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0923
S=0: data transfer completed
M=0: AS-i master 1
x9 = reflected user ID 9
23 = reflected command number 35
2
0
604
or
8
604
06 = slave address shifted by 1 bit to the left
→
3 * 2 = 6
04 = 4 bytes ID data to be sent
the most significant bit (TG) changes after each execution
3…18 0000
not
changed
NOTE
•
The number of bytes to be sent must be divisible by 2 since the system always transmits only
multiples of 2 bytes in the S7.4 protocol.
•
The control bytes defined in profile 7.4 with follow and valid bits are completed by the system.
Therefore, without segmentation, this command is limited to 20 bytes of parameter data. Larger
data volumes must be divided into segments.
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...