DP module 12: Extended command channel
Module 12, acyclic command 36 dec (24hex):
standard read call of an AS-i slave with CTT2 profile
(S-7.5.5, S-7.A.5 or S-B.A.5)
9-43
Response from controllere (gateway) in case of an error
(error detected by AS-i slave)
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=1
S
0/1
M
0/1
reflected user ID
reflected command number = 24
hex
2
TG 0
reserved
F=1
reserved
3
CTT2 error code
error code = E1
3…18
not changed
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 8424
E=1: error during command execution
M=0: AS-i master 1
x4 = reflected user ID changes e.g. to -
24 = reflected command number 36
2
0100
or
8100
F=1: error during command execution
the most significant bit (TG) changes after each execution
3 01E1
CTT2 error code 01 = invalid index,
→
data sheet of the AS-i slave
error code E1 = error detected by AS-i slave; CTT2 error
4…18 0000
ignored
Possible CTT2 error codes
Value [hex]
Description
00 no
error
01 invalid
index
02 invalid
length
03
command not implemented
04
occupied, command could not be completed in the specified time
05
command was not acknowledged
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...