DP module 12: Extended command channel
Module 12, extended command 10...20dec (0A...14hex):
force analogue data transfer directly to / from 3 AS-i slaves in each case
9-22
Response from controllere (gateway)
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=0 B=0
M
0/1
reflected user ID
reflected command number = 0A…14
hex
3
input data or reflected output data AS-i slave 1(A), channel 0
4
input data or reflected output data AS-i slave 1(A), channel 1
5
input data or reflected output data AS-i slave 1, channel 2 or
input data or reflected output data AS-i slave 1B, channel 0
6
input data or reflected output data AS-i slave 1, channel 3 or
input data or reflected output data AS-i slave 1B, channel 1
7
TIB TOB TIA TOA
TVB
OVB TVA OVA O3 V3 O2 V2 O1 V1 O0 V0
8
input data or reflected output data AS-i slave 2(A), channel 0
9
input data or reflected output data AS-i slave 2(A), channel 1
10
input data or reflected output data AS-i slave 2, channel 2 or
input data or reflected output data AS-i slave 2B, channel 0
11
input data or reflected output data AS-i slave 2, channel 3 or
input data or reflected output data AS-i slave 2B, channel 1
12
TIB TOB TIA TOA
TVB
OVB TVA OVA O3 V3 O2 V2 O1 V1 O0 V0
13
input data or reflected output data AS-i slave 3(A), channel 0
14
input data or reflected output data AS-i slave 3(A), channel 1
15
input data or reflected output data AS-i slave 3, channel 2 or
input data or reflected output data AS-i slave 3B, channel 0
16
input data or reflected output data AS-i slave 3, channel 3 or
input data or reflected output data AS-i slave 3B, channel 1
17
TIB TOB TIA TOA
TVB
OVB TVA OVA O3 V3 O2 V2 O1 V1 O0 V0
18
not changed
Legend
→
page
and
OVA
channel-independent data valid flag of the A slave / standard slave:
OVA=0: the last valid data transfer took place more than 3.5 s ago (TT1) or:
the slave has not received new output values (CTT2...5)
OVA=1: within max. 3 seconds the slave requests new data (CTT1) or:
the slave has received new output values (CTT2...5)
OVB
channel-independent data valid flag of the B slave (from master profile M4 onwards):
OVB=0: the slave has not received new output values
OVB=1 slave has received new output values
Note:
valid only for reflected output data
TVA
channel-independent data valid flag of the A slave / standard slave:
TVA=0: transmission error or timeout occurred
TVA=1: analogue data transfer under way
TVB
channel-independent transmission valid flag of the B slave (from master profile M4 onwards):
TVB=0: transmission error or timeout occurred
TVB=1: analogue data transfer under way
Note:
since this flag evaluates the data transfer cycle which was last completed the response is delayed by up
to 140 ms
more
→
next page
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...