Set-up
Device-specific Profibus DP parameters
7-25
7.4
Device-specific Profibus DP parameters
With up to 100 bytes of the device-specific Profibus parameters the addresses of the analogue input
slaves and analogue output slaves to be transferred in parallel can be defined and the parameters of
the connected AS-i slaves can be set.
7.4.1
Device-specific Profibus DP parameters (example)
Byte
Parameter
[hex]
Description
1 80
2 00
3 00
4 00
fixed device parameters
5
AE
fixed value: start of the analogue input addresses
6
…
20
42
…
slaves 2, 4, 6, 8,...30 of master 1
21
AA
fixed value: start of the analogue output addresses
22
…
36
41
…
slaves 1, 3, 5, 7,...29 of master 1
2F
bit 5 = TRUE activates the extended diagnosis of the AS-i system via Profibus DP
37
1F
bit 4 = TRUE activates the AS-i parameter download
37
…
100
1F
…
FF
predefined parameters of the AS-i slaves
Slave addresses in the Profibus parameter bytes 6…20 and 22...36
Bit:
7
6
5
4
3
2
1
0
MM X
SSSSS
Legend
MM
2 bits
Master no.
1…2
X
1 bit
Slave type
0 = single or A slave
1 = B slave
SSSSS
5 bits
Slave no.
1…31
dec
Calculation of the more significant byte (MMXSSSSS):
(slave no.) + (master no. * 64
dec
) + (32
dec
, if B slave)
Examples:
Master 1
Slave 3(A)
1*64 + 3
= 67
dec
= 43
hex
Master 2
Slave 5(A)
2*64 + 5
= 133
dec
=
85
hex
Master 1
Slave 1B
1*64 + 1 + 32
= 97
dec
= 61
hex
Master 1
Slave 28(A)
1*64 + 28
= 92
dec
= 5C
hex
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...