The DPV1 command channel
DPV1 command 34dec (22hex):
read the parameter string of an AS-i slave with the profile S-7.4
11-35
Example:
Word no.
Value [hex]
Description
1 086F
08 = reflected user ID 8
6F = command status is "ready" (no fault)
2
0622
or
8622
06
hex
= 00
00 011
0
2
→
slave address = 3(A),
22
hex
= reflected command number 34
dec
the most significant bit TG changes after each execution
3
1234
1st word of the parameter string of slave 3(A)
4
5678
2nd word of the parameter string of slave 3(A)
… …
…
18
0004
4-byte parameter string was read