The DPV1 command channel
DPV1 command 33dec (21hex):
read diagnosis string of an AS-i slave with the profile S-7.4
11-33
Response from controllere (DPV1 slave)
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
reflected user ID
command status = 6F
hex
2
TG S
AS-i slave address
F
reflected command number = 21
hex
3
diagnosis string 1
diagnosis string 0
4…16
diagnosis strings 2...27
17
diagnosis string 29
diagnosis string 28
18
00
number of bytes received
Legend
→
page
NOTE
The control bytes defined in profile 7.4 with follow byte and valid byte are filtered out by the system.
Example:
Word no.
Value [hex]
Description
1 076F
07 = reflected user ID 7
6F = command status is "ready" (no fault)
2
0621
or
8621
S=0
→
last sequence,
06
hex
= 00
00 011
0
2
→
slave address = 3(A),
21
hex
= reflected command number 33
dec
the most significant bit TG changes after each execution
3
2D01
1st word of the diagnosis data of slave 3(A)
4
0203
2nd word of the diagnosis data of slave 3(A)
5
1122
3rd word of the diagnosis data of slave 3(A)
6
3344
4th word of the diagnosis data of slave 3(A)
… …
…
18
0008
8 bytes diagnosis data
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...