Set-up
Parameter setting of the Profibus host
7-15
Module 2: Binary inputs/outputs of single / A slaves of AS-i master 2
Contents
Binary inputs and outputs of single or A slaves of AS-i master 2
Length
0...16 bytes I/O (if not used: length = 0)
Byte no.
Bits 4...7
Bits 0...3
1 flags
master
2
slave1(A)
2 slave2(A)
slave3(A)
3 slave4(A)
slave5(A)
4 slave6(A)
slave7(A)
5 slave8(A)
slave9(A)
6 slave10(A)
slave11(A)
7 slave12(A)
slave13(A)
8 slave14(A)
slave14(A)
9 slave16(A)
slave15(A)
10 slave18(A)
slave19(A)
11 slave20(A)
slave21(A)
12 slave22(A)
slave23(A)
13 slave24(A)
slave25(A)
14 slave26(A)
slave27(A)
15 slave28(A)
slave29(A)
16 slave30(A)
slave31(A)
The flags in the first input byte contain status information of AS-i master 2:
Bit 7
Bit 6
Bit 5
Bit 4
PLC running in the
controllere
Configuration error
in the AS-i circuit
No AS-i slave
detected
Periphery fault
The flags in the first output byte contain control information of the AS-i master 2:
Bit 7
Bit 6
Bit 5
Bit 4
Reserved Reserved
Reset of the stored
diagnostic data
Activate transfer of
the stored
diagnostic data
If bit 4 of the control information is TRUE, the controllere transmits the stored periphery faults and
configuration errors in the device-specific diagnosis. The flags remain TRUE even if the fault or error is
no longer present. Bit 5 in the control information resets this information.
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...