The DPV1 command channel
DPV1 command 9dec (09hex):
change the extended ID code 1 in the connected AS-i slave
11-17
Response from controllere (DPV1 slave) in case of an error
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
reflected user ID
command status = 6B
hex
2
00
reflected command number = 09
hex
3
00 error
code
Example:
Word no.
Value [hex]
Description
1 0F6B
0F = reflected user ID changes e.g. to 15
6B = error during command execution
2
0009
09 = reflected command number 9
3 0007
error code 07
hex
→
slave does not support the extended ID code
Possible error codes
Error code
Name
Description
01 NOK
no slave response or
master is in the offline mode when calling the command
02
SND
no slave with the address found
03
SD0
slave with address 0 connected
07
SE
error when writing the extended ID code 1
09
ET
extended ID code 1 could only be saved temporarily
0B ia
address is invalid
or: 2 slaves with address 0 detected
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...