DP module 12: Extended command channel
Module 12, extended command 34dec (22hex):
read parameter character string of an AS-i slave with the profile S-7.4
9-37
9.19
Module 12, extended command 34
dec
(22
hex
):
read parameter character string of an AS-i slave with the profile S-7.4
Request of DP master
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
R
S
0/1
M
0/1
user ID
command number = 22
hex
= 34
dec
2
reserved = 0
reserved = 0
3
R R R
slave
address
R R R
data
length
4…18
not used
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0822
0xxx = command only requests 1 data packet
M=0: AS-i master 1
08 = user ID changes e.g. to 8
22 = command number 34
2 0300
03 = slave address 3
00 = data length = 0
Response from controllere (gateway)
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=0
S
0/1
M
0/1
reflected user ID
reflected command number = 21
hex
2
TG
R
slave address
F=0
R
R
number of bytes to be received
3
parameter character string 1
parameter character string 0
4…16
parameter character string 2...27
17
parameter character string 29
parameter character string 28
18
reserved
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0822
data transfer completed
M=0: AS-i master 1
08 = reflected user ID 8
22 = reflected command number 34
2
0
604
or
8
604
x6 = slave address 3 shifted 1 bit to the left
→
3 * 2 = 6
04 = 4 byte ID data
the most significant bit (TG) changes after each execution
3
1234
1st word of the parameter character string of slave 3
4
5678
2nd word of the parameter character string of slave 3
5…18 0000
reserved
Note:
The control bytes defined in profile 7.4 with follow and valid bits are filtered out by the system.
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...