Acyclic services for Profibus DPV1
Examples
10-5
10.5 Examples
10.5.1
Examples DPV1 reading
DPV1 master request
Received data DPV1 master
Slot
Index Length Data field
Data length [bytes]
0
0
0
M1 digital slave inputs %IB1.1…%IB11.31
64
0
0
2
M1 digital slave inputs %IB1.1…%IB1.2
2
0
0
60
M1 digital slave inputs %IB1.1…%IB11.27
60
0
3
0
M1 current configuration data %IW31.0…%IW31.63
128
0
3
6
M1 current configuration data %IW31.0…%IW31.2
6
10.5.2
Examples DPV1 writing
DPV1 master request
Received data DPV1 slave
Slot
Index Length Data field
Data length [bytes]
0
7
2
M1 digital slave outputs %QB1.1…%QB1.2
2
0
8
10
M1 analogue slave outputs %QW21.1.0…%QW21.1.5
10
0
11
12
M1 command channel request
12
10.6 DPV1
error
messages
10.6.1
DPV1 error code application
Error byte 1
[hex]
Description
A0 Read
error
A1 Write
error
A2 Module
failure
A8 Version
conflict
A9
Feature not supported
AA User
specific
10.6.2
DPV1 error codes data access
Error byte 1
[hex.]
Description
B0 Invalid
index
B1
Write length error
B2 Invalid
slot
B3 Type
conflict
B4 Invalid
area
B5 Status
conflict
B6 Access
denied
B7 Invalid
range
B8 Invalid
parameter
B9 Invalid
type
BA…BF User
specific
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...