DP module 12: Extended command channel
Module 12, extended command 53dec (35hex):
read current configuration of the AS-i slaves 16B...31B
9-58
9.28
Module 12, extended command 53
dec
(35
hex
):
read current configuration of the AS-i slaves 16B...31B
Request of DP master
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
R R
M
0/1
user ID
command number = 35
hex
= 35
dec
2
reserved = 0
reserved = 0
3…18
not used
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0535
M=0: AS-i master 1
05 = user ID changes e.g. to 5
35 = command number 53
Response from controllere (gateway):
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=0 B=0
M
0/1
reflected user ID
reflected command number = 35
hex
2
reserved = 0
reserved = FF
hex
3
Slave 16B: ID2
Slave 16B: ID1
Slave 16B: ID code
Slave 16B: IO config.
4
Slave 17B: ID2
Slave 17B: ID1
Slave 17B: ID code
Slave 17B: IO config.
5…17
… … … …
18
Slave 31B: ID2
Slave 31B: ID1
Slave 31B: ID code
Slave 31B: IO config.
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0535
M=0: AS-i master 1
05 = reflected user ID changes e.g. to 5
35 = reflected command number 53
2 00FF
reserved
3 FFFF
current configuration of slave 16B
ID2 = F, ID1 = F, ID = F, IO = F
→
slave is not present
4 EF03
current configuration of slave 17B
ID2 = E, ID1 = F, ID = 0, IO = 3
… …
…
18 EF37
current configuration of slave 31B
ID2 = E, ID1 = F, ID = 3, IO = 7
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...