DP module 12: Extended command channel
Module 12, extended command 6:
readdress a connected AS-i slave
9-16
Response from controllere (gateway) in case of an error
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=1 B=0
M
0/1
reflected user ID
reflected command number = 06
hex
2
reserved = 0
reserved = 0
3
0 error
code
4…18
ignored
Legend
→
page
Example:
Word no.
Value [hex]
Description
1
8
806
E=1: fault occurred during execution of the command
M=0: AS-i master 1
88 = reflected user ID 8
06 = reflected command number 6
2 0000
reserved
3
0003
error code 03
hex
= slave with the address 0 connected
Possible error codes
Value [hex]
Description
01
no slave response or:
master is in the offline mode when calling the command
02
no slave with the old address found
03
slave with address 0 connected
04
no slave with the new address found
05
error when deleting the old address
06
error when reading the IO configuration
07
error when writing the new address or the extended ID code 1
08
new address could only be saved temporarily
09
extended ID code 1 could only be saved temporarily
0B
parameter or address invalid
14
master is in the wrong operating mode
here: master is not in the normal mode
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...