The DPV1 command channel
DPV1 command 58dec (3Ahex):
read projected configuration of the AS-i slaves 1B…15B
11-63
11.30
DPV1 command 58
dec
(3A
hex
):
read projected configuration of the AS-i slaves 1B…15B
Request of DPV1 master
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
user ID
command request = 65
hex
2
00
command number = 3A
hex
= 58
dec
3…17
ignored
18…19
reserved
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0265
02 = user ID changes e.g. to 2
65 = command request
2
003A
3A = command number 58
Response from controllere (DPV1 slave)
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
reflected user ID
command status = 6F
hex
2
00
reflected command number = 3A
hex
3
F
hex
F
hex
F
hex
F
hex
4
slave1B, ID2
slave1B, ID1
slave1B, ID code
slave1B, IO conf.
5...17
... ... ... ...
18
slave15B, ID2
slave15B, ID1
slave15B, ID code
slave15B, IO conf.
Example:
Word no.
Value [hex]
Description
1 026F
02 = reflected user ID 2
6F = command status is "ready" (no fault)
2
003A
3A = reflected command number 58
3
FFFF
here not used since slave 0B cannot be projected
4 EF03
projected configuration of slave 1B:
ID2 =E, ID1=F, ID=0 and IO=3
… …
…
18 EF37
projected configuration of slave 15B:
ID2 =E, ID1=F, ID=3 and IO=7
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...