Acyclic services for Profibus DPV1
DPV1 addresses in slot 0 for access via PLC
10-4
DPV1 addresses in slot 0
Byte no.
Index
from
to
Contents
Access
r = read
w = write
Size
[words]
IEC addresses
0
31
M2 reflected parameters
r
16
%IW32.160…%IW32.175
32
155
M2 slave error counter
r
62
%IW32.176…%IW32.237
156
157
M2 configuration error counter
r
1
%IW32.238
22
158
159
M2 AS-i cycle counter
r
1
%IW32.239
0
63
M2 digital slave outputs
r/w
32
%QB2.1…%QB2.31
%QB12.1…%QB12.31
23
64 67
M2
reserved
2
–
24
0
149
M2 analogue slave outputs
r/w
75
%QW22.1.0…%QW22.15.4
25
0
159
M2 analogue slave outputs
r/w
80
%QW22.16.0…%QW22.31.4
0
127
M2 projected configuration data
r/w
64
%QW32.0…%QW32.63
26
128
159
M2 projected parameters
r/w
16
–
27
0
37
M2 command channel request
r/w
19
–
28
0
37
M2 command channel response
r
19
–
32
0
127
Input data of the fieldbus
r/w
64
%IW0.0…%IW0.63
33
0
127
Output data to the fieldbus
r
64
%QW0.0…%QW0.63
34 0 127
Extended data to the controllere PLC
r/w 64
%IW4.0…%IW4.63
35 0 127
Extended data to the controllere PLC
r/w 64 %IW4.64…%IW4.127
36 0 127
Extended data to the controllere PLC
r/w 64 %IW4.128…%IW4.191
37 0 127
Extended data to the controllere PLC
r/w 64 %IW4.192…%IW4.255
38 0 127
Extended data from the controllere PLC
r 64 %QW4.0…%QW4.63
39 0 127
Extended data from the controllere PLC
r 64 %QW4.64…%QW4.127
40 0 127
Extended data from the controllere PLC
r 64 %QW4.128…%QW4.191
41 0 127
Extended data from the controllere PLC
r 64 %QW4.192…%QW4.255
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...