DP module 12: Extended command channel
Module 12, acyclic command 39dec (27hex):
manufacturer-specific write call of an AS-i slave with CTT2 profile
(S-7.5.5, S-7.A.5 or S-B.A.5)
9-51
9.24
Module 12, acyclic command 39
dec
(27
hex
):
manufacturer-specific write call of an AS-i slave with CTT2 profile
(S-7.5.5, S-7.A.5 or S-B.A.5)
– available from master profile M4 onwards –
Request of DP master
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
R
S
0/1
M
0/1
user ID
command number = 27
hex
= 39
dec
2
R R
A/B
0/1
slave address
reserved = 0
3
number of bytes to be sent
Index
4
parameter byte 1
parameter byte 0
5…17
parameter bytes 2...27
18
parameter byte 29
parameter byte 28
Legend
→
page
and
Index
Pointer to the page to be read
Length: 1 byte
Permitted values: 0…255
dec
(0…FF
hex
)
Description:
→
data sheet of the addressed CTT2 slave
Number of
bytes to be
sent
Number of bytes to be sent
Length: 1 byte
Permitted values: 1…30
dec
(01…1E
hex
)
Description:
→
data sheet of the addressed CTT2 slave
Example:
Word no.
Value [hex]
Description
1 0727
M=0: AS-i master 1
07 = user ID changes e.g. to 7
27 = command number 39
2
0300
03 = slave address 3(A)
3
0207
in index 7, 2 parameter bytes are to be written
4
1AF4
both parameter bytes for slave 3(A)
5…18 0000
not
used
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...