DP module 12: Extended command channel
Module 12, extended command 9:
change extended ID code 1 in the AS-i slave
9-19
Response from controllere (gateway) in case of an error
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=1 B=0
M
0/1
reflected user ID
reflected command number = 09
hex
2
reserved = 0
reserved = 0
3
0 error
code
4…18
ignored
Legend
→
page
Example:
Word no.
Value [hex]
Description
1
8
F09
E=1: fault occurred during execution of the command
M=0: AS-i master 1
8F = reflected user ID 15
09 = reflected command number 9
2 0000
reserved
3 0007
error code 07
hex
= error when writing the new address or the extended ID code 1
here: slave does not support the extended ID code 1
Possible error codes
Value [hex]
Description
01
no slave response or:
master is in the offline mode when calling the command
02
no slave with the old address found
03
slave with address 0 connected
07
error when writing the new address or the extended ID code 1
09
extended ID code 1 could only be saved temporarily
0B
parameter or address invalid
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...