DP module 12: Extended command channel
Module 12, extended command 50dec (32hex):
read current configuration of AS-i slaves 0(A)...15(A)
9-55
9.25
Module 12, extended command 50
dec
(32
hex
):
read current configuration of AS-i slaves 0(A)...15(A)
Request of DP master
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
R R
M
0/1
user ID
command number = 32
hex
= 50
dec
2
reserved = 0
reserved = 0
3…18
not used
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0232
M=0: AS-i master 1
x2 = user ID changes e.g. to 2
32 = command number 50
Response from controllere (gateway)
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
E=0 B=0
M
0/1
reflected user ID
reflected command number = 32
hex
2
reserved = 0
reserved = FF
hex
3
Slave 0(A): ID2
Slave 0(A): ID1
Slave 0(A): ID code
Slave 0(A): IO config.
4
Slave 1(A): ID2
Slave 1(A): ID1
Slave 1(A): ID code
Slave 1(A): IO config.
5…17
… … … …
18
Slave 15(A): ID2
Slave 15(A): ID1
Slave 15(A): ID code
Slave 15(A): IO config.
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0232
M=0: AS-i master 1
2 = reflected user ID changes e.g. to 2
32 = reflected command number 50
2 00FF
reserved
3 FFFF
Current configuration slave 0(A)
ID2 = F, ID1 = F, ID = F, IO = F
→
slave is not present
4 EF03
Current configuration slave 1(A)
ID2 = E, ID1 = F, ID = 0, IO = 3
… …
…
18 EF37
Current configuration slave 15(A)
ID2 = E, ID1 = F, ID = 3, IO = 7
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...