DP module 12: Extended command channel
Error codes in the module 12
9-5
9.3
Error codes in the module 12
Value [hex]
Description
01
no slave response or:
master is in the offline mode when calling the command
02
no slave with the old address found
03
slave with address 0 connected
04
no slave with the new address found
05
error when deleting the old address
06
error when reading the IO configuration
07
error when writing the new address or the extended ID code 1
08
new address could only be saved temporarily
09
extended ID code 1 could only be saved temporarily
0A
slave is not in LAS
0B
parameter or address invalid
0C
faulty S-7.4 protocol sequence
0D
S-7.4 protocol aborted (timeout)
0E
invalid AS-i slave address for the S-7.4 protocol (e.g. B slaves)
0F
AS-i slave has completed the S-7.4 string
10
AS-i S-7.4 no longer connected (no longer in LAS)
11
another S-7.4 transfer to the addressed AS-i slave is already active
12
the previous segmented S-7.4 transfer was not completed
13
invalid S-7.4 data length
14
master is in the wrong operating mode or
invalid S-7.4 command
16
timeout during command processing
17
wrong slave profile or
slave not in LAS
master is not in the normal mode
20
the command could not be processed within the specified time
E0...EF
error detected by AS-i slave; note error code CTT2 (see below)
F0
invalid CTT2 command
F1
invalid CTT2 response
F2
7.5 data length longer than 30 bytes
9.4
CTT2 error code in module 12
Value [hex]
Description
00 no
error
01 invalid
index
02 invalid
length
03
command not implemented
04
occupied, command could not be completed in the specified time
05
command was not acknowledged
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...