DP module 12: Extended command channel
Module 12, extended command 4:
write LPS
9-11
9.8
Module 12, extended command 4:
write LPS
Request of DP master
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
R R
M
0/1
user ID
command number = 04
hex
= 04
dec
2
reserved = 0
3
15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) res.
4
31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)
5
15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B res.
6
31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B
7…18
not used
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0204
M=0: AS-i master 1
02 = user ID changes e.g. to 2
04 = command number 4
2 0000
reserved
3 001E
slaves 1(A) to 5(A) *) are to be projected
001E
hex
= 0000 0000 0001 1110
bin
4 8000
slave 31(A) *) is to be projected
8000
hex
= 1000 0000 0000 0000
bin
5
0002
slave 1B *) is to be projected
6
0001
slave 16B *) is to be projected
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...