The DPV1 command channel
DPV1 command 21dec (15hex):
read ID string of an AS-i slave with the profile S-7.4
11-25
Response from controllere (DPV1 slave) in case of an error
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
reflected user ID
command status = 6B
hex
2
00
reflected command number = 15
hex
3
00 error
code
Example:
Word no.
Value [hex]
Description
1 026B
02 = reflected user ID 2
6B = error during command execution
2
0015
15 = reflected command number 21
3 0014
error code 14
hex
→
master is not in the normal mode
Possible error codes
Value [hex] Description
0C
faulty S-7.4 protocol sequence
0D
S-7.4 protocol aborted (timeout)
0E
invalid AS-i slave address for the S-7.4 protocol (e.g. B slaves)
0F
AS-i slave has completed the S-7.4 string
10
AS-i S-7.4 no longer connected (no longer in LAS)
11
to this AS-i slave another S-7.4 transfer is already active
12
previous segmented S-7.4 transfer not yet completed
13
invalid S-7.4 data length
14
invalid S-7.4 command
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...