Set-up
Parameter setting of the Profibus host
7-23
Module 8: data transfer between Profibus DP master and PLC in the controllere
Contents
Field for the data transfer between the Profibus DP master system and the PLC
functions in the controllere
Length
0...64-word inputs (if not used: length = 0)
Module 9: data transfer between PLC in the controllere and Profibus DP master
Contents
Field for the data transfer between the PLC functions in the controllere and the
Profibus DP master system
Length
0...64-word outputs (if not used: length = 0)
Module 10: parallel analogue inputs
Parallel analogue inputs of up to 30 AS-i slaves, 1/2/4 words per AS-i slave; the
slave number and the number of analogue channels can be defined by Profibus
DP parameters.
Data length = 4 words
(preset) All 4 channels of a total of up to 15 slaves on master 1 and 2 are
transmitted.
Selection of the slaves to be transmitted via Profibus DP device
parameters (
→
Device-specific Profibus DP parameters
,
page
Data length = 2 words
From slave 1 (of up to 30 slaves) on master 1 onwards, the channels 1
and 2 are transmitted.
Contents
Data length = 1 word
From slave 1 (of up to 30 slaves) on master 1 and 2 onwards, channel 1
is transmitted.
Length
0...60-word inputs (if not used: length = 0)
Module 11: parallel analogue outputs
Parallel analogue outputs of up to 30 AS-i slaves, 1/2/4 words per AS-i slave; the
slave number and the number of analogue channels can be defined by Profibus
DP parameters.
Data length = 4 words
(preset) All 4 channels on a total of up to 15 slaves on master 1 and 2
are transmitted.
Selection of the slaves to be transmitted via Profibus DP device
parameters (
→
Device-specific Profibus DP parameters
,
page
Data length = 2 words
On slave 1 (up to 30 slaves) on master 1, the channels 1 and 2 are
transmitted.
Contents
Data length = 1 word
On slave 1 (up to 30 slaves) on master 1 and 2 , channel 1 is
transmitted.
Length
0...60-word outputs (if not used: length = 0)
NOTE
If analogue outputs are also triggered in module 6, the value written in module 6 is overwritten with
the data of module 11.
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...