Set-up
Parameter setting of the Profibus host
7-11
7.3.2
Assign PLC addresses to the Profibus modules
What are "Profibus modules"? These are entries in a parameter setting database of the programming
software for the Profibus DP master system (host). There you assign the individual "modules" to the
virtual "locations".
Locations are address areas for certain functions.
Modules are placeholders for certain address quantities within these areas.
The following IEC addresses are the designations for the PLC addresses in the controllere:
IEC address area
from
to
Description
Data flow
AS-i host
DP module
%IB1.1
%IB1.31
master 1, slaves 1A...31A, digital inputs
→
1 input
%IB2.1
%IB2.31
master 2, slaves 1A...31A, digital inputs
→
2 inputs
%IB11.1
%IB11.31
master 1, slaves 1B...31B, digital inputs
→
3 input
%IB12.1
%IB12.31
master 2, slaves 1B...31B, digital inputs
→
4 input
%IW21.1.x %IW21.31.x
master 1, slaves 1...31,
analogue inputs x = channel*)
→
5 and 10
%IW22.1.x %IW22.31.x
master 2, slaves 1...31,
analogue inputs x = channel *)
→
5 and 10
%IW0.0 %IW0.63
DP
outputs
for signal preprocessing
←
9
%IB0.128 %IB0.143
DP outputs for master1, slaves 1A...31A,
digital outputs
←
1 output
%IB0.144 %IB0.159
DP outputs for master1, slaves 1B...31B,
digital outputs
←
3 output
%IB0.160 %IB0.175
DP outputs for master2, slaves 1A...31A,
digital outputs
←
2 output
%IB0.176 %IB0.191
DP outputs for master 2, slaves 1B...31B,
digital outputs
←
4 output
%IW0.96 %IW0.219
DP outputs for master 1, slaves 1...31,
analogue outputs
←
11
%IW0.224 %IW0.347
DP outputs for master 2, slaves 1...31,
analogue outputs
←
11
%IB0.704 %IB0.719
DP parameters for master 1, slaves
1A...31A, parameter data
←
DP
parameters
%IB0.720 %IB0.735
DP parameters for master 1, slaves
1B...31B, parameter data
←
DP
parameters
%IB0.736 %IB0.751
DP parameters for master 2, slaves
1A...31A, parameter data
←
DP
parameters
%IB0.752 %IB0.767
DP parameters for master 2, slaves
1B...31B, parameter data
←
DP
parameters
%QB1.1 %QB1.31
master 1, slaves 1A...31A,
digital outputs
→
–
%QB2.1 %QB2.31
master 2, slaves 1A...31A,
digital outputs
→
–
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...