The DPV1 command channel
DPV1 command 1dec (01hex):
write parameters to a connected AS-i slave
11-5
11.4
DPV1 command 1
dec
(01
hex
):
write parameters to a connected AS-i slave
Request of DPV1 master
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
user ID
command request = 65
hex
2
0
command number = 01
hex
= 1
dec
3
ignored
A/B
AS-i slave address
4
ignored
parameter value to
be written
5…19
ignored
Legend
→
page
Example:
Word no.
Value [hex]
Description
1 0965
09 = user ID changes e.g. to 9
65 = command request
2
0001
01 = command number 1
3
0024
slave address 4B (for B slave: addition of 20
hex
or 32
dec
to the slave address)
4
0003
parameter value to be written