Set-up
Parameter setting of the Profibus host
7-20
Module 7: Command channel
Contents
Command
channel
→
page
Length
4-byte consistent I/O (if not used: length = 0)
IMPORTANT:
For the query read only the required bytes. Unused bytes can
contain information of previous queries.
DP master request (4 bytes)
Bit
Byte
7
6
5
4
3
2
1
0
1
Command no.
2
MM X
SSSSS
3
→
Tables starting on the next page
4
→
Tables starting on the next page
Calculation (MMXSSSSS):
(slave no.) + (master no. * 64
dec
) + (32
dec
, if B slave)
Controllere response (4 bytes, copy of the request)
Bit
Byte
7
6
5
4
3
2
1
0
1
D7 D6
Command
no.
2
MM X
SSSSS
3
→
Tables starting on the next page
4
→
Tables starting on the next page
Legend
D7
1 bit
Error code
0 = no error occurred
1 = error occurred during command processing
D6
1 bit
Command code
0 = command processed, buffer response valid
1 = command being processed, channel occupied
MM
2 bits
Master no.
1...2
X
1 bit
Slave type
0 = single or A slave
1 = B slave
SSSSS
5 bits
Slave no.
1…31
dec
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...