Troubleshooting
Service manual
45
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
3.3.38 E5-00 – Outdoor unit: Overheat of inverter compressor motor
Trigger
Effect
Reset
Compressor overload is
detected.
Unit will NOT stop
operating.
Automatic reset if the unit
runs without warning for
60 seconds.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check that all stop valves of the refrigerant circuit are open. See
Possible cause:
Closed stop valve in the refrigerant circuit.
2
Perform
a
check
of
the
discharge
pipe
thermistor.
See
217].
Possible cause:
Faulty discharge pipe thermistor or connector fault.
3
Perform a check of the outdoor unit fan motor. See
197].
Possible cause:
Faulty outdoor unit fan motor.
4
Perform a check of the compressor. See
148].
Possible cause:
Faulty compressor or miswiring of the compressor power
supply cable.
5
Perform a check of the expansion valve. See
162].
Possible cause:
Faulty expansion valve.
6
Perform a check of the 4‑way valve. See
Possible cause:
Faulty 4‑way valve.
7
Perform a check of the main PCB. See
184].
Possible cause:
Faulty main PCB.
8
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant shortage.
9
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
256].
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
10
Check if the refrigerant circuit is clogged. See
Possible cause:
Clogged refrigerant circuit.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
draft – 31/05/2022 15:53