Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.A.2
[D-09]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
6: 100 pulse/kWh (PV meter)
7: 1000 pulse/kWh (PV meter)
└─
Sensors
9.B.1
[C-08]
R/W
0: No
1: Outdoor
2: Room
9.B.2
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
9.B.3
[1-0A]
R/W
0: No
1: 12 h
2: 24 h
3: 48 h
4: 72 h
└─
Bivalent
9.C.1
[C-02]
R/W
0: NO
1: Yes
9.C.2
[7-05]
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
9.C.3
[C-03]
R/W
-25~25°C, step: 1°C
0°C
9.C.4
[C-04]
R/W
2~10°C, step 1°C
3°C
Installer settings
9.D
[C-09]
R/W
0: Abnormal
1: Normal
9.E
[3-00]
R/W
0: manual
1: automatic
9.F
[E-08]
R/W
0: No
1: Yes
9.G
R/W
0: No
1: Yes
└─
Overview field settings
9.I
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
[2-0C]=0
25°C
[2-0C]=1
35°C
[2-0C]=2
40°C
9.I
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
[2-0C]=0
35°C
[2-0C]=1
45°C
[2-0C]=2
60°C
9.I
[0-02]
R/W
10~25°C, step: 1°C
15°C
9.I
[0-03]
R/W
-40~5°C, step: 1°C
-10°C
9.I
[0-04]
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0C]=0
18°C
[2-0C]=1
7°C
[2-0C]=2
18°C
9.I
[0-05]
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0C]=0
22°C
[2-0C]=1
15°C
[2-0C]=2
22°C
9.I
[0-06]
R/W
25~43°C, step: 1°C
35°C
9.I
[0-07]
R/W
10~25°C, step: 1°C
20°C
9.I
[0-0B]
R/W
35~[6-0E]°C, step: 1°C
55°C
9.I
[0-0C]
R/W
Min(45~[6-0E])
~
[6-0E]°C, step: 1°C
60°C
9.I
[0-0D]
R/W
10~25°C, step: 1°C
15°C
9.I
[0-0E]
R/W
-40~5°C, step: 1°C
-10°C
9.I
[1-00]
R/W
-40~5°C, step: 1°C
-10°C
9.I
[1-01]
R/W
10~25°C, step: 1°C
15°C
9.I
[1-02]
R/W
[9-01]~[9-00], step: 1°C
[2-0C]=0
35°C
[2-0C]=1
45°C
[2-0C]=2
60°C
Boiler efficiency
Temperature
Electricity meter 2 / PV meter
External sensor
Ext. amb. sensor offset
Averaging time
Bivalent
Hysteresis
Alarm output
Auto restart
Power saving function
Disable protections
Leaving water value for high ambient temp. for LWT add zone
heating WD curve.
Leaving water value for low ambient temp. for LWT add zone
heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone
cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone
cooling WD curve.
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone
heating WD curve.
4P685235-1 - 2022.03
(*1) EBLA*_(*2) EDLA*_(*3) *23V3_(*4) *2V3