12/14
Breadcrumb
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.I
[9-0C]
R/W
1~6°C, step: 0,5°C
1 °C
9.I
[9-0D]
R/W
0~8, step:1
0 : No limitation
1~4 : 90~60% pump speed
5~8 : 90~60% pump speed during
sampling
6 80% pump speed
9.I
[9-0E]
6
9.I
[C-00]
R/W
0: Solar priority
1: Heat pump priority
9.I
[C-01]
0
9.I
[C-02]
R/W
0: NO
1: Yes
9.I
[C-03]
R/W
-25~25°C, step: 1°C
0°C
9.I
[C-04]
R/W
2~10°C, step 1°C
3°C
9.I
[C-05]
R/W
1: 1 contact
2: 2 contacts
9.I
[C-06]
R/W
1: 1 contact
2: 2 contacts
9.I
[C-07]
R/W
0: Leaving water
1: External room thermostat
2: Room thermostat
9.I
[C-08]
R/W
0: No
1: Outdoor
2: Room
9.I
[C-09]
R/W
0: Abnormal
1: Normal
9.I
[C-0A]
0
9.I
[C-0B]
0
9.I
[C-0C]
0
9.I
[C-0D]
0
9.I
[C-0E]
0
9.I
[D-00]
R/W
0: No
1: Only BSH
2: Only BUH
3: All
9.I
[D-01]
R/W
0: No
1: Open
2: Closed
3: Smart Grid
9.I
[D-02]
R/W
0: No DHW pump
1: Instant hot water
2: Disinfection
3: Circulation
4: Circulation and disinfection
9.I
[D-03]
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
9.I
[D-04]
R/W
0: No
1: Pwr consmp ctrl
9.I
[D-05]
R/W
0: No
1: Yes
9.I
[D-07]
R/W
0: No
1: Yes (DHW)
9.I
[D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
9.I
[D-09]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
6: 100 pulse/kWh (PV meter)
7: 1000 pulse/kWh (PV meter)
9.I
[D-0A]
2
9.I
[D-0B]
2
9.I
[D-0C]
0
9.I
[D-0D]
0
9.I
[D-0E]
0
9.I
[E-00]
R/O
0~5
2: Monobloc
9.I
[E-01]
R/O
0
9.I
[E-02]
R/W (*1)
R/O (*2)
0: Reversible (*1)
1: Heating only (*2)
9.I
[E-03]
R/O (*3)
R/W (*4)
0: No heater (*4)
1: External heater
2: 3V (*3)
9.I
[E-04]
R/O
0: No
1: Yes
9.I
[E-05]
R/W
0: No
1: Yes
9.I
[E-06]
1
Bivalent hysteresis temperature.
What is the thermo request contact type for the main zone?
What is the thermo request contact type for the add. zone?
What is the unit control method in space operation?
Is an external backup heat source connected?
Bivalent activation temperature.
Room temperature hysteresis.
Pump speed limitation
Leaving water temperature compensation around 0°C.
What is the indoor unit software type?
Which type of external sensor is installed?
What is the required alarm output contact type?
--
--
Domestic heating water priority.
--
Can the system prepare domestic hot water?
Is an external kWh meter used for power measurement, kWh
meter used for smart grid?
--
--
--
Which heaters are permitted if prefer. kWh rate PS is cut?
Contact type of preferential kWh rate PS installation?
--
--
Which type of DHW pump is installed?
Which type of unit is installed?
Is a demand PCB connected?
--
--
Is the pump allowed to run if prefer. kWh rate PS is cut?
Is a solar kit connected?
Is an external kWh meter used for power measurement?
--
--
--
Is the power saving function available on the outdoor unit?
What is the number of backup heater steps?
Which type of compressor is installed?
4P685235-1 - 2022.03
(*1) EBLA*_(*2) EDLA*_(*3) *23V3_(*4) *2V3