![background image](http://html1.mh-extra.com/html/daikin/ebla04e-v-series/ebla04e-v-series_service-manual_4704429178.webp)
4
|
Components
Service manual
178
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
4.12.2 Repair procedures
To correct the wiring from the main power supply terminal to the hydro PCB
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Remove the required plate work, see
202].
2
Make sure that all wires are firmly and correctly connected, see
281].
3
Check the continuity of all wires.
4
Replace any damaged or broken wires.
Is the problem solved?
Action
Yes
No further actions required.
No
and continue with the next procedure.
To remove the hydro PCB
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Remove the required plate work, see
202].
2
Disconnect all connectors and the ground wire from the hydro PCB.
3
Carefully pull the hydro PCB and unlatch the PCB supports one by one using a
small pliers.
draft – 31/05/2022 15:53