4
|
Components
Service manual
229
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
e
d
f
f
a
Clip
b
Thermistor
c
Thermistor holder
d
Insulation
e
Thermistor wire
f
Tie strap
2
Install the insulation around the thermistor.
3
Fix the insulation and the thermistor wire using new tie straps.
INFORMATION
See the overview of the thermistors at the start of the electrical check procedure and
the
281] to determine if the specific thermistor is either:
▪
Directly connected to the PCB
▪
Connected to an intermediate connector which is connected to the PCB
4
If connected to an intermediate connector, connect the thermistor connector
to the intermediate connector. If directly connected to the PCB, connect the
thermistor connector to the appropriate PCB.
WARNING
When reconnecting a connector to the PCB, make sure to connect it on the correct
location and do NOT apply force, as this may damage the connector or connector
pins of the PCB.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
4.19.3 Other thermistors
Checking procedures
To perform a mechanical check of the external thermistor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
draft – 31/05/2022 15:53