3
|
Troubleshooting
Service manual
65
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
3.3.67 L8-00 – Malfunction triggered by a thermal protection in the main PCB
Trigger
Effect
Reset
When compressor
overload (except during
start-up) is detected.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check that all stop valves of the refrigerant circuit are open. See
Possible cause:
Closed stop valve in the refrigerant circuit.
2
Check if the refrigerant circuit is clogged. See
Possible cause:
Clogged refrigerant circuit.
3
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant overcharge or shortage.
4
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
256].
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
5
Perform a check of the main PCB. See
184].
Possible cause:
Faulty main PCB.
6
Perform a check of the compressor. See
148].
Possible cause:
Faulty compressor or miswiring of the compressor power
supply cable.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.3.68 L9-00 – Prevention of compressor lock
Trigger
Effect
Reset
Detection of start‑up
failure after time passed
to avoid compressor lock.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the compressor. See
148].
Possible cause:
Faulty compressor or miswiring of the compressor power
supply cable.
draft – 31/05/2022 15:53