5
|
Third party components
Service manual
256
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
5.1.2 Repair procedures
To adjust the power supply
1
Make sure that the power source is in line with the requirements described in
the databook.
2
Adjust the power supply within 50 Hz ± 3%.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To correct the wiring between PCB's
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
202].
1
Make sure that all wires are firmly and correctly connected, see
281].
2
Check the continuity of all wires.
3
Replace any damaged or broken wires.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
5.2 Refrigerant circuit
5.2.1 Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To check if the stop valves are open
Prerequisite:
Remove the required plate work, see
202].
1
Remove the caps.
draft – 31/05/2022 15:53
Summary of Contents for EBLA04E V Series
Page 322: ...14 14...
Page 323: ......