Third party components
Service manual
271
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Place the air purge valve, installed inside the unit, in the open position by
turning it clockwise.
INFORMATION
If a backup heater kit is installed, place the air purge valve of the backup heater kit in
the open position.
a
A
B
b
b
a
A
Unit with built‑in backup heater
B
Unit without backup heater
a
Manual air purge valve
b
Automatic air purge valve
2
Place all field installed air purge valves in the open position.
3
Purge the water circuit, see
269].
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To install the field installed air purge valves on the highest points of the water circuit
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Install field installed air purge valves on all highest points of the installation
outside the unit.
2
Purge the water circuit, see
269].
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To purge the water circuit
1
Check that all field installed air purge valves are installed in the correct
locations, see
2
See
"To open the air purge valves of the water circuit"
270] for detailed
information about the unit air purge valves.