4
|
Components
Service manual
239
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
2
Disconnect the other end of the wiring harness from the hydro PCB.
3
Cut all tie straps that fix the wiring harness, and remove the wiring harness
from the unit.
4
To install the water flow sensor wiring harness, see
238].
To install the water flow sensor wiring harness
1
Connect the wiring harness to the connector X34A on the hydro PCB.
2
Route the wiring harness towards the water flow sensor and connect the
wiring harness to the water flow sensor.
3
Fix the wiring harness using new tie straps.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To remove the water flow sensor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Remove the required plate work, see
2
Drain the water circuit, see
269].
3
Loosen the water flow sensor connector nut.
c
a
b
b
a
Water flow sensor connector nut
b
Clip
c
Water flow sensor
4
Unplug the water flow sensor harness from the water flow sensor.
5
Remove the 2 clips that fix the water flow sensor.
6
Remove the water flow sensor.
7
Clean any spilled water.
8
To install the new water flow sensor, see