3.3.37 E4-00 – Abnormal suction pressure
Trigger
Effect
Reset
Suction pressure was too
low (detected by
thermistor/pressure
sensor or low pressure
switch) for several times.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform
a
check
of
the
suction
pipe
thermistor.
See
Possible cause:
Faulty suction pipe thermistor or connector fault.
2
Check that all stop valves of the refrigerant circuit are open. See
256].
Possible cause:
Closed stop valve in the refrigerant circuit.
3
Check if the refrigerant circuit is correctly charged. See
256].
Possible cause:
Refrigerant shortage.
4
Check for the presence of humidity in the refrigerant circuit. See
256].
Possible cause:
Humidity in the refrigerant circuit.
5
Check if the refrigerant circuit is clogged. See
256].
Possible cause:
Clogged refrigerant circuit.
6
Perform a check of the expansion valve. See
Possible cause:
Faulty expansion valve.
7
Check the required space around the outdoor unit heat exchanger. See
Possible cause:
Insufficient air flow or air by‑pass due to required space
specifications not met.
8
Clean the outdoor heat exchanger. See
Possible cause:
Dirty outdoor heat exchanger.
9
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.