4
|
Components
Service manual
217
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
4.19 Thermistors
4.19.1 Refrigerant side thermistors
Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a mechanical check of the specific thermistor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Locate the thermistor and remove the insulation if needed. Check that the
thermistor is correctly installed and that there is thermal contact between the
thermistor and the piping or ambient (for air thermistor).
Is the thermistor correctly installed
(thermal contact between the
thermistor and the piping)?
Action
Yes
Perform an electrical check of the
specific thermistor, see
217].
No
Correctly install the thermistor, see
To perform an electrical check of the specific thermistor
1
First perform a mechanical check of the thermistor, see
217].
2
Locate the thermistor.
INFORMATION
Remove the thermistor from its holder if not reachable with a contact thermometer.
3
Measure the temperature using a contact thermometer.
Name
Symbol
Location (PCB) Connector
(pins)
Reference
(table)
Air thermistor
R1T
Main
S90: 1‑2
A
Heat
exchanger
thermistor
R2T
Main
S90: 3‑4
A
Discharge pipe
thermistor
R3T
Main
S90: 5‑6
B
Refrigerant
liquid
thermistor
R3T
Hydro
X7A: 1‑2
A
4
Determine the thermistor resistance that matches the measured
temperature.
draft – 31/05/2022 15:53