4
|
Components
Service manual
158
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
a
a
Compressor wire terminals cover
13
Install the compressor insulation, see
14
15
Add
refrigerant
to
the
refrigerant
circuit,
see
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
4.8 Compressor thermal protector
4.8.1 Checking procedures
To perform a mechanical check of the compressor thermal protector
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
202].
Prerequisite:
Remove the compressor insulation.
1
Remove the cover of the compressor wire terminals.
draft – 31/05/2022 15:53