4
|
Components
Service manual
170
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
11
Again measure the resistance on the (disconnected) flow switch connector.
Result:
The flow switch MUST be closed (0 Ω).
INFORMATION
When water flow is below flow switch trigger set point, switch MUST be open (OL).
When water flow is above flow switch trigger set point, switch MUST be closed (0 Ω).
Are flow switch measurements
correct?
Action
Yes
Flow switch is OK. Return to
troubleshooting of the specific error
and continue with the next procedure.
No
Replace the flow switch, see
4.10.2 Repair procedures
To remove the flow switch
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
202].
1
2
Unscrew the flow switch and remove it from the piping.
a
b
a
Flow switch
b
Piping
3
Disconnect the flow switch harness connector from the hydro PCB.
4
Cut all tie straps that fix the wiring harness.
5
Guide the flow switch harness out of the switch box and remove the flow
switch.
6
To install the flow switch, see
To install the flow switch
1
Install (screw) the flow switch on correct location on the piping and in the
correct orientation (arrow pointing in the direction of the water flow). Ensure
that the O-ring is correctly installed and NOT damaged.
draft – 31/05/2022 15:53