EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
To recuperate the refrigerant
Prerequisite:
Stop the unit operation via the user interface.
1
Manually open all expansion valves.
2
Connect the vacuum pump, manifold, recovery unit, and refrigerant bottle to
the service port of the refrigerant circuit as shown below.
H
V
R
L
c
b
a
a
Vacuum pump
b
Connect flexible hose to service port
c
To recovery pump
L
Low pressure
H
High pressure
V
Vacuum
R
Refrigerant
3
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To add refrigerant
1
See the installer reference guide for the correct procedure.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to troubleshooting of the
specific error and continue with the
next procedure.