![background image](http://html1.mh-extra.com/html/daikin/ebla04e-v-series/ebla04e-v-series_service-manual_4704429249.webp)
4
|
Components
Service manual
249
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
Is the problem solved?
Action
Yes
No further actions required.
No
Return to
245] of the water pump
and continue with the next procedure.
To remove the water pump motor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Disconnect the connectors from the water pump motor.
a
d
a
b
b
c
a
Connector
b
Bolt
c
Water pump motor
d
Pump housing
2
Remove the 4 bolts that fix the water pump motor to the pump housing.
3
Separate the water pump motor from the pump housing.
4
Remove the water pump motor.
5
To install the water pump motor, see
248].
To install the water pump motor
1
Install the motor on the water pump housing.