4
|
Components
Service manual
222
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
e
d
f
f
a
Clip
b
Thermistor
c
Thermistor holder
d
Insulation
e
Thermistor wire
f
Tie strap
INFORMATION
Some of the thermistors are wired to the same connector. See connector and pin
information of the thermistors at the start of the electrical check procedure and
281]. ALWAYS replace the complete set of thermistors wired
to the same connector.
2
When installing the complete set of thermistors wired to the same connector:
▪
Install all other thermistors wired to the connector in their thermistor
holder,
▪
Route the thermistor harness of all thermistors towards the appropriate PCB
or intermediate connector,
▪
Connect the thermistor connector.
WARNING
When reconnecting a connector to the PCB, make sure to connect it on the correct
location and do NOT apply force, as this may damage the connector or connector
pins of the PCB.
3
Fix the thermistor harness using new tie straps
4
Install the insulation around the thermistor.
5
Fix the insulation and the thermistor wire using new tie straps.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.