4
|
Components
Service manual
160
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
8
Again measure the resistance on the compressor thermal protector.
Result:
The contact MUST be closed (measured resistance = 0 Ω).
Does the compressor thermal protector
contact open and close at the correct
temperature?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Replace the compressor thermal
protector, see
4.8.2 Repair procedures
To remove the compressor thermal protector
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
202].
Prerequisite:
Remove the compressor insulation.
1
Remove the cover of the compressor wire terminals.
a
a
Compressor wire terminals cover
2
Remove the compressor thermal protector with bracket from the compressor
housing.
draft – 31/05/2022 15:53