4
|
Components
Service manual
149
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
To perform a mechanical check of the compressor
Prerequisite:
First perform an auditive check of the compressor, see
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Before proceeding:
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see
2
Visually check:
▪
For oil drops around the compressor. Locate and fix as needed.
▪
Pipes for signs of damage. Replace pipes as needed.
3
Check that the compressor bolts are correctly fixed. Fix as needed.
4
Check that the compressor wire terminals cover is correctly installed and
fixed. Correct as needed.
5
Check the compressor dampers for any damage.
a
a
a
Damper
INFORMATION
The compressor dampers may look different.
Compressor dampers are in a good
condition?
Action
Yes
Perform an electrical check of the
compressor, see
148].
No
Replace the compressor and/or
damaged dampers, see
153].